FULLTEST 3
EN - 7
RCD test
- AC, A and B type.
- General, selective and delayed characteristic.
- Voltage range 100 ... 265 V.
- Limit contact voltage 25 or 50 V.
- IN = 10, 30, 100, 300, 500, 650 or 1000 mA.
- Trip out time at IN/2 (AC, A and B type).
- Trip out time at IN (AC, A and B type).
- Trip out time at 2IN (AC and A type).
- Trip out time at 5IN (AC and A type) or at 4IN (B type).
- Ramp test (AC, A and B type).
- AUTO test (AC, A and B type).
- Visual and acoustic warning in case of exceeded limit value.
EN61557-6
Loop impedance measurement
- ZL/N, ZL/L and ZL/PE measurement.
- Voltage range 100 460 V.
- IPSC calculation.
- Limit value adjustable, visual and acoustic warning in case of exceeded
value.
EN60204-1-§18.2
EN61557-3
Global earth resistance
- Selectable test current with regard to involved RCD.
- IN = 10, 30, 100, 300, 500, 650 or 1000 mA.
- Measurement with IN/2 (without tripping out RCD)
- Voltage range 100 265 V.
- Contact voltage UC measured during the measurement.
- Limit value (RA) fixed to 25 or 50 V/IN, visual and acoustic warning in
case of exceeded value.
Residual voltage
- Measurement on power plug (2-wire method).
- Measurement on internal components (4-wire method).
- Limit discharge time 1 s or 5 s.
- LINEAR or NONLINEAR mode.
- Visual and acoustic warning in case of exceeded limit value.
EN60204-1-§18.5
Power (on schuko socket)
- Apparent power P
APP.
- Real power P.
- Mains voltage U
L/N.
- Load current IL.
- Power factor PF.
- Leakage current IPE (differential method).
- Internal phase position exchange.
- Limit value (apparent power) adjustable, visual and acoustic warning in
case of exceeded value.
Phase sequence
- Mains voltages UL1/2, UL2/3, UL3/1 simultaneously displayed.
EN61557-7